Solar Energy Input
- Max. PV Array Power: 165,000 Wp STC
- Max. Input Voltage: 1100 V
- MPPT Voltage Range / Rated Input Voltage: 200 V - 1000 V / 630 V
- Min. Input Voltage: 200 V
- Initial Feed-in Voltage: 250 V
- Max. Operating Input Current: 32 A per MPPT
- Max. Short Circuit Current: 48 A per MPPT
- No. of Independent MPPT Inputs / Strings per MPPT Input: 10 / 2
AC Output (Grid)
- Rated Active Power: 110 kW
- Rated Apparent Power: 110,000 VA
- Max. Apparent Power: 121,000 VA
- AC Nominal Voltage: 220 V / 380 V, 230 V / 400 V
- AC Voltage Range: 312 V - 528 V
- AC Grid Frequency / Range: 50 Hz / 45 Hz - 55 Hz, 60 Hz / 55 Hz - 65 Hz
- Max. Output Current: 174.7 A
- Adjustable Power Factor Range: 0.8 leading to 0.8 lagging
- Feed-in Phases: 3 / 3-N-PE
- Harmonic Distortion (THD) at Rated Output: < 3%
Efficiency and Protection
- Max. Efficiency / European Efficiency: 98.6% / 98.4%
- DC Switch: Yes
- Ground Fault Monitoring / Grid Monitoring: Yes / Yes
- DC Reverse Polarity Protection / AC Short Circuit Protection: Yes / Yes
- AC Overcurrent Protection: Yes
- DC Surge Protection: Type II
- AC Surge Protection: Type II
- Residual Current Monitoring Unit: Yes
- Arc Fault Circuit Interrupter (AFCI): Optional
- Anti-Islanding Protection: Yes
- Protection Class (IEC 62109-1) / Overvoltage Category (IEC 62109-1): I / AC: III; DC: II
General Data
- Dimensions (W × H × D): 984 × 640 × 330 mm
- Weight: 86 kg
- Topology: Non-isolated
- Self-Consumption (Night): < 3 W
- Operating Temperature Range: -25°C to +60°C
- Degree of Protection (IEC 60529): IP66
- Cooling Concept: Active cooling
- Max. Operating Altitude: 4000 m
- Climatic Category (IEC 60721-3-4): 4K4H
- Max. Relative Humidity: 100% (non-condensing)
Features
- DC Connection: DC Plug-in connector
- AC Connection: OT/DT Terminal (Max. 240 mm²)
- LED Indicators (Status / Fault / Communication): Yes
- 24/7 Monitoring: Yes
- Communication Interface: RS485 / Wi-Fi / LAN / Optional 4G
- Modbus-Sunspec Protocol: Yes
Certifications and Standards
- Certificates and Approvals: CE, IEC 62109-1/2, IEC 61727, IEC 62116, IEC61683, EN50549-1/2, VDE4105